Filtrans Services |
|
| |
Removal of all suspended particles such as dust, rust, scales, colloidal carbon oxidation sludge, etc up to <1 unicorn, degassing and dehydration of transformer oil under vaccum, circulation of heated oil and filling of treated oil in transformer tank, de-acidification by evaporation and absorption method is a must for ensuring prolonged service life a transformer.
Transformer Oil Filtration Machine
|
• Medium High Vacuums Single Stage JMHV Model Filter Machine
• Capacity - 3000 liters per hour
• Vacuum - Ultra High Vacuum less than 1m bar
• Filter rating - 1 micron
01 no.
|
PERFORMANCE OF ABOVE SAID OIL CONDITIONING PLANT
| Oil conditioning flow rate liters / hour ( LPH ) |
: 3000 |
| Degree of filtration in microns |
: 1 micron |
PARAMETERS Unprocessed Oil Quality
|
| Di-electric strength |
: 20 KV |
| Moisture content |
: 80 PPM |
| Gas content in percentage by volume |
: 6% |
Conditioned Oil Quality After Single Pass
|
| Di-electric strength |
: 60 KV |
| Moisture content |
: 10 PPM |
| Gas content in percentage by volume |
: 1% |
Conditioned Oil Quality After Multi Pass
|
|
| Di-electric strength |
: 70 KV |
| Moisture content |
: 5 PPM |
| Gas content in percentage by volume |
: 0.2 % |
| |
|
| ∙ Low Vacuum Filter Machine |
|
| ∙ Capacity - 600 Liter per Hour 01 no. |
|
|
|
|
|
|
|